IMD 100 Integration manual 4189360015 Rev. G
Electrical HW connections and requirements
Page 49 of 243
Terminal no.
Terminal text
Description
16
DI 11
Digital input 11,
(reserved for manual operation “+“ [CW]
if manual operation is enabled configuration)
17
DI 12
Digital input 12, (reserved for manual
operation “Manual
e
nable“ if manual operation is enabled configuration)
18
0 V
Ground
Recommended connections for manual operation:
DI 10
DI 11
DI 12
+24 V DC
5.5.2 Connecting safety I/O and digital outputs (X8)
X8 connector contains safety-chain inputs and outputs, additional relay output (RO), and eight digital
outputs.
The wires are connected to the female connector as follows:
Terminal no.
Terminal text
Description
1
SCI 1.1
Safety-chain input channel 1 (+)
Attention
The digital inputs are galvanically isolated from the IMD circuit by optocouplers. Ground
from the external circuit must be connected to terminal 18.