IMD 100 Integration manual 4189360015 Rev. G
Operational procedures
Page 164 of 243
8. Click on Device
→
Flash… to open the upgrade dialogue:
9. Ensure that all three checkboxes are ticked and click Start.
10. When the programming cycle is completed, set the IMD back to normal operation mode:
a. Turn the 24 V DC (or the 400 V AC if the DC power supply is built-in) off.
b. Set the CAN ID switch back to its original position.
c. Turn the 24 V DC (or the 400 V AC if the DC power supply is built-in) on. Note that the first
startup after firmware upgrade might take longer (up to approximately 10 s).
11. The IMD is now updated.
9.16.3 Updating firmware through CANopen
9.16.3.1
Prerequisites
•
A specific
“FW updater” SW must be implemented (by the customer) in the Pitch Motion Controller,
or Turbine Controller (see section
on page
•
Instructions on how to use the implemented “FW updater” SW available
•
Bootloader for CANopen FW update is installed on the IMD (see section
•
The turbine must be stopped in a safe position and all blades are in fully feathered position.
9.16.3.2
Updating the firmware
1. Update the firmware according the
“FW updater” instructions
2. When all IMDs are updated the turbine can be restarted
Info
On rare occasions, The SDFlash program will show a “Connection error” after step
is executed. In such a case, it is necessary to restart the whole process:
11.
Close the SDflash program
12. Turn off the IMD
13. Start the SDflash
14. Turn on the IMD
15. Repeat com configuration, and the actions described in steps