IMD 100 Integration manual 4189360015 Rev. G
Parameter description
Page 229 of 243
Sub
object
ID
Parameter name
Ser. / CAN
Type
Function
Range
Unit
Factory
default
Data
type
Access
7
SETUP_MODE
Configuration Sets the charger in and out of
Setup mode.
0x5555: Setup mode
Any other value: not in
programming mode
NUM
0
U16
RW
8
BUCONTROL
Configuration Save and load parameters to /
from EEPROM.
0x1111: Save parameters
from RAM to EEPROM
0x1113: Load parameters
from EEPROM to RAM
NUM
0
U16
RW
10
START_STOP
Function
Start and stop charging. When
stop is executed, state changes
to ready and waits for start
command.
0: Stop
1: Start
NUM
1
U16
rW
14
VOLTAGE_IMD_SE
Status
SE voltage measurement by the
IMD.
0 .. 65535
0.1 V
N/A
U16
RO
15
SE_STORAGE_TYPE
Configuration Selection of SE storage type.
0: None
1: Lead acid
2: Lithium Ion
3: Ultra capacitor
N/A
0
U16
RW
16
SE_NOM_VOLTAGE
Configuration The nominal voltage of the SE
from which all other voltage
limits are derived.
0 .. 65535
0.1 V
0
U16
RW
17
SE_MAX_CURRENT
Configuration Base current from which all
other current limits are derived.
0 .. 65535
0.01 A
0
U16
RW
18
BULKCHARGEENDVOLTAGE
Configuration End voltage for bulk stage in
percentage of
SE_NOM_VOLTAGE
(Values
above 100% can also be used).
0 .. 65535
0.01%
0
U16
RW
19
BULKCHARGECURRENT
Configuration Bulk stage constant current in
percentage
SE_MAX_CURRENT
.
0 .. 65535
0.01%
0
U16
RW