IMD 100 Integration manual 4189360015 Rev. G
Electrical HW connections and requirements
Page 48 of 243
The digital input wires are connected to the female connector as follows:
Terminal no.
Terminal text
Description
1
RFE
Rotational Field Enable, intended to be used as safe
torque off for emergency stop buttons. Disables the
power module and engages the brake. Use a normally
closed switch connected to +24 V DC.
2
RUN
Device enable. If in motion, the motor actively
decelerates and brake sequence started. If not in motion
the device is disabled and the motor brake is engaged.
3
LS 1
Limit switch 1 (active high or low is configurable)
4
LS 2
Limit switch 2 (active high or low is configurable)
5
DI 1
Digital input 1
6
DI 2
Digital input 2
7
DI 3
Digital input 3
8
DI 4
Digital input 4
9
0 V
Ground
10
DI 5
Digital input 5
11
DI 6
Digital input 6
12
DI 7
Digital input 7
13
DI 8
Digital input 8
14
DI 9
Digital input 9
, (reserved for manual operation 360 “360
enabled” if manual operation 360 is enabled in the
configuration)
15
DI 10
Digital input 10, (
reserved for manual operation “-“ [CCW]
if manual operation is enabled in the configuration)