IMD 100 Integration manual 4189360015 Rev. G
IMD configuration
Page 118 of 243
10. Save the configuration to the EEPROM (see IMD Manager user manual).
8.6.2 Configuring additional motor parameters
The additional motor parameters are the electrical properties of the motor. There are two ways this
can be done:
•
Enter the data from the data sheet manually (if available)
. If this is done, “L sigma-q” value must be
filled before “L sigma-d” value.
•
Use the automatic calculation procedure (calculates the parameter values using data from the
name plate).
The following procedure describes how to use the automatic calibration procedure.
8.6.2.1 Prerequisites
Before configuring the additional para
meters all the fields in the “Motor data” group in “Configuration
1/3” tab must be filled.
8.6.2.2 Calculation procedure
1.
Select “[Fn8] Calc from motor nameplate” in the “Special function” group in the “Configuration 3/3”
tab.
2.
Click on “START” button
Attention
If the motor type is
Sync. Servo
, all configurable parameters in
“Additional motor
parameters” must be set to zero.