IMD 100 Integration manual 4189360015 Rev. G
IMD configuration
Page 105 of 243
In this parameter settings, settling time is
very long. On the other hand, the overshoot
is very small. The Ti parameter is relatively
low (20), which causes the motor to
oscillate.
Legend: Black: N cmd (ramp)
Blue: N actual
Legend: Black: N cmd (ramp)
Blue: N actual
Legend: Black: N cmd (ramp)
Blue: N actual
The Ti parameter is set higher (60). Settling
time is shorter. On the other hand, the
overshoot is slightly higher.
The Kp parameter is set lower (1). Settling
time is shorter. On the other hand, the
overshoot is slightly higher.