IMD 100 Integration manual 4189360015 Rev. G
Errors and warnings
Page 192 of 243
12.2
Warning list
When a warning is active it is displayed in the IMD Manager tool in the “Warning(s)” field. Following is
a list of warnings:
Table 30
Warning list and description
Warning
bit no.
IMD Manager
Warning(s) field
Warning description
0
BADPARA
Parameter error. This warning can be caused by the following
reasons:
•
Deceleration ramp too long
when “Run” signal is deactivated
•
Calculation of motor-parameters gives an unlikely result
1
Warning 1
Not used
2
Warning 2
Not used
3
COMCHARGER
Communication error with the built-in charger (option).
If this warning persists for the Charger timeout period, and the
IMD is configured to escalate charger warnings to error, error
3 will be generated.
Sending “clear errors” every 8 seconds will delay error
generation (until clearing errors is stopped) if the warning
persists.
4
FEEDBACK
Unstable resolver signal. This warning is also active during blind
safety run.
5
POWERVOLTAGE
Safe energy voltage is lower than SE Vmin.
6
MOTORTEMP
--Motor temperature high. Motor-temperature reached 87.5% of the
limit specified in
M-temp
.
7
DEVICETEMP
IMD temperature high.
Internal components temperature exceeded 72 ºC.
8
Warning 8
Not used
9
I_PEAK
Digital output driver is overheated
A
Warning A
Not used
B
CHARGER
Error in the charger (option).
There are a number of charger errors that caused the warning that
was escalated to the error. These can be determined by reading the
charger error register.
If this warning persists for the Charger timeout period, and the IMD
is configured to escalate charger warnings to error, error 3 will be
generated.
Sending “clear errors” every 8 seconds will delay error generation
(until clearing errors is stopped) if the warning persists.
C
HIGHVOLTAGE
Ballast resistor is on too long (> 100 ms) while the Mains is ON. If
the pitch controller does not act for more than 5 seconds, a
HIGHVOLTAGE error is generated, and the warning is reset.