IMD 100 Integration manual 4189360015 Rev. G
IMD configuration
Page 124 of 243
4. Enter the charge current parameter value. This value is the 100% current value. All other current
parameters’ values are defined as percentage of this value.
NOTE
Resolution in any current setting is 10 mA. This applies to all current charge values. If this
or any resulting current is above 5 A, the charger will use 5 A.
5. According to the selected SE type, go to the applicable step:
b. Lithium Ion: Section
NOTE
When entering a value in percent, the resulting voltage in Volt or current in Ampere, will be
shown after hitting “Enter” or moving the cursor to another field. There is no restraint on the
percentage values (may be above 100%).
8.7.3.2 Configuration of Lead acid SE type parameters:
Lead acid charging process:
•
Bulk stage: Charging starts in Bulk stage with constant current (
Bulk current
). The Bulk stage
continues until the voltage reaches
Absorption voltage
, and the charger goes to absorption stage.
•
Absorption stage: Charging is done with constant voltage (
Absorption voltage
) until the current
drops to
Absorp.end current
, and the charger goes to float stage.
•
Float stage: This is the final stage. Charging is done with constant voltage (
Float voltage
).