IMD 100 Integration manual 4189360015 Rev. G
Operational procedures
Page 141 of 243
9.9.3 Operation
N/A
9.9.4 Deactivation
Once initiated, a safety run cannot be deactivated. It stops only by activation of a limit switch, or
timeout.
9.10
Normal operation
Normal operation is the state where the IMD controls the motor under normal conditions.
9.10.1 Prerequisites
The IMD must be in either Start up at park (3) or Parked ready (17) states.
RFE and RUN inputs (X9, terminals 1 and 2) must be high.
Safety chain inputs must be OK.
9.10.2 Activation
IMD Manager:
Click on the “Enable dev.” button:
CAN/CANopen:
changes the “Enable dev.” (reg. 0x51 bit 2) to “0” (on).
9.10.3 Operation
While in normal operation mode, is possible to disable and enable the drive by SW (reg. 0x51 bit 2), or
HW (RUN input, X9-terminal 2). Both SW and HW must be enabled in order to enable the drive.
When the drive is disabled, the output to the motor goes to zero, and the brake output is deactivated
(+24 off). The “Dev. Enabled” and “GO” flags are set to zero.
9.10.4 Deactivation
Only errors and special commands will take the IMD out of the normal operation mode.
9.11
Pre-heating the motor
Activating the pre-heat function is done by using function 02 in the special functions.
9.11.1 Prerequisites
The Device must be disabled (reg. 0x51 bit 2 = 1).
The IMD must be in one of the following states: