IMD 100 Integration manual 4189360015 Rev. G
Electrical HW connections and requirements
Page 28 of 243
Shield to PE
Shield to Ground
1
5
6
9
PE
connection
GND
connection
Shield
GND
connection
(pigtail ended
shield)
Shrink
tubes
1
5
6
9
Shield & Ground
to PE
GND
connection
(pigtail ended
shield)
Shrink
tubes
1
5
6
9
PE
connection
Recommended
NOT
recommended
Do not use
Figure 17
Realization of shielding in connectors
5.2
Power connections (X1)
Disconnect power
Ensure that all power is disconnected when connecting cables to the IMD. If the IMD was
powered, wait at least 5 minutes after the power is disconnected, due to residual voltage in
the IMD.
Phoenix PLH16 connector is used for connections in X1 (direct connector).
Phoenix SPT 2.5 connector is used for R-BALLAST connections in IMD 122 C equipped with External
ballast resistor option.
Attention
The use of shield to ground (with a pigtail) is not recommended.
Do not use shield to ground (with a pigtail) and to PE
Danger!
Risk of burns and electrical shock from short circuit, electrical arc and uninsulated wires.
Live work is not permitted, except for during commissioning and service.
Observe local regulation when working with electrical components.