3
|
Components
Service manual
190
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
VDC
Com
Ref
VDC
Com
Ref
U
CB+
0.560 V
CB+
U
O.L
V
CB+
0.560 V
CB+
V
O.L
W
CB+
0.560 V
CB+
W
O.L
CB-
U
0.560 V
U
CB-
O.L
CB-
V
0.560 V
V
CB-
O.L
CB-
W
0.560 V
W
CB-
O.L
Are the test results OK?
Action
Yes
Power modules are OK. Return to
main PCB and continue with the next
procedure.
No
Problem solved?
After all checking procedures listed above have been performed:
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
Repair procedures
To remove the main PCB
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
1
Remove the required plate work, see
230].
DANGER: RISK OF ELECTROCUTION
Confirm the rectifier voltage is below 10 V DC before proceeding, see
285].
2
Remove (or flip over) the protective cover sheet.
3
Unplug the compressor U, V and W Faston connectors from the main PCB.
4
Unplug the L1C, L2C and L3C Faston connectors from the main PCB.