2
|
Troubleshooting
Service manual
26
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
2.3.21 C0-00 – Flow sensor malfunction
Trigger
Effect
Reset
Water flow sensor detects
water flow 45 seconds
after the water pump has
stopped.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Possible cause:
Water pressure is too low.
2
Possible cause:
Water flow is too low.
3
Possible cause:
Air in the water circuit.
4
Check the water circuit for an external pump. See
Possible cause:
The detected water flow is caused by an external pump.
5
Perform an electrical check of the water flow sensor. See
Possible cause:
Faulty water flow sensor.
6
Perform a check of the hydro PCB. See
Possible cause:
Faulty hydro PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.22 C4-00 – Heat exchanger temperature sensor problem
Trigger
Effect
Reset
Refrigerant liquid
thermistor detects an
open or short circuit
during compressor
operation.
Unit will stop operating.
Power reset.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform
a
check
of
the
refrigerant
liquid
thermistor.
See
Possible cause:
Faulty refrigerant liquid thermistor.