2
|
Troubleshooting
Service manual
31
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
5
Check for the presence of non‑condensables and/or humidity in the
refrigerant circuit. See
286].
Possible cause:
Non‑condensables and/or humidity in the refrigerant circuit.
6
Check if the refrigerant circuit is clogged. See
Possible cause:
Clogged refrigerant circuit.
7
Perform a check of the outdoor unit fan motor. See
217].
Possible cause:
Faulty outdoor unit fan motor.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.28 E4-00 – Abnormal suction pressure
Trigger
Effect
Reset
Suction pressure was too
low (detected by
thermistor/pressure
sensor or low pressure
switch) for several times.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform
a
check
of
the
suction
pipe
thermistor.
See
248].
Possible cause:
Faulty suction pipe thermistor or connector fault.
2
Check that all stop valves of the refrigerant circuit are open. See
Possible cause:
Closed stop valve in the refrigerant circuit.
3
Check if the refrigerant circuit is correctly charged. See
Possible cause:
Refrigerant shortage.
4
Check for the presence of humidity in the refrigerant circuit. See
Possible cause:
Humidity in the refrigerant circuit.
5
Check if the refrigerant circuit is clogged. See
Possible cause:
Clogged refrigerant circuit.
6
Perform a check of all expansion valves. See
149].
Possible cause:
Faulty expansion valve.
7
Check the required space around the outdoor unit heat exchanger. See
307].
Possible cause:
Insufficient air flow or air by‑pass due to required space
specifications not met.