Troubleshooting
Service manual
21
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check the water pressure. See
299].
Possible cause:
Water pressure is too low.
2
Check the water flow. See
299].
Possible cause:
Water flow is too low.
3
Check that all stop valves of the water circuit are open. See
Possible cause:
Closed stop valve in the water circuit.
4
Purge the water circuit. See
299].
Possible cause:
Air in the water circuit.
5
Perform a check of the outdoor air thermistor. See
248].
Possible cause:
Faulty ambient air thermistor.
6
Perform a check of all expansion valves. See
149].
Possible cause:
Faulty expansion valve.
7
Check that all stop valves of the refrigerant circuit are open. See
Possible cause:
Closed stop valve in the refrigerant circuit.
8
Check if the refrigerant circuit is clogged. See
Possible cause:
Clogged refrigerant circuit.
9
Check if the refrigerant circuit is correctly charged. See
Possible cause:
Refrigerant overcharge or shortage.
10
Check for the presence of non‑condensables and/or humidity in the
refrigerant circuit. See
286].
Possible cause:
Non‑condensables and/or humidity in the refrigerant circuit.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.16 AA-01 – Backup heater overheated
Trigger
Effect
Reset
Thermal protector is
activated. Measured
water temperature too
high.
Unit will stop operating.
Manual reset via user
interface and manual
reset of backup heater
thermal protector.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.