4
|
Third party components
Service manual
306
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
To remove the external heat source from the water circuit
1
Remove the external heat source from the installation outside the unit.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To install a by-pass in the water circuit
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
1
Install a by‑pass in the water circuit outside the installation as shown below.
b
c
a
d
e
a
By‑pass
b
Underfloor heating (cooling) circuit
c
Radiators circuit
d
Indoor or outdoor unit
e
Space heating (cooling) water circuit
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To replace the leaking domestic hot water tap in the water circuit
1
Replace the leaking domestic hot water tap in the water circuit with a correct
one.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To repair the leak in the water circuit
1
Repair the leak in the water circuit.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.