Troubleshooting
Service manual
36
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
Possible cause:
▪
Faulty or disturbance of the power supply (imbalance >4%),
▪
Power drop,
▪
Short circuit.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.34 EA-00 – Outdoor unit: Cool/heat switchover problem
Trigger
Effect
Reset
Room thermistor is NOT
functioning within
operation range.
Unit will NOT stop
operating.
Automatic reset after a
continuous operation for
some time.
If the error occurs too
soon: unit will stop
operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the 4‑way valve. See
96].
Possible cause:
Faulty 4‑way valve.
2
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB.
3
Perform a check of the room thermistor:
▪
Measure the room temperature and compare to the room temperature
shown on the user interface (remote controller).
▪
If temperature shown on the user interface differs from the measured
temperature, replace the user interface (remote controller). See
documentation of the user interface (remote controller) for more
information.
Possible cause:
Faulty room thermistor.
4
Check the communication wiring between the remote controller and the unit.
See
Possible cause:
Faulty wiring between the remote controller and the unit.
5
Perform a check of the hydro PCB. See
Possible cause:
Faulty hydro PCB.
6
Check that all stop valves of the refrigerant circuit are open. See
286].
Possible cause:
Closed stop valve in the refrigerant circuit.
7
Check if the refrigerant circuit is clogged. See
286].
Possible cause:
Clogged refrigerant circuit.