3
|
Components
Service manual
171
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
Is the problem solved?
Action
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
3.14 Main PCB
3.14.1 Single fan outdoor unit - single phase
Checking procedures
INFORMATION
It is recommended to perform the checks in the listed order.
To perform a power check of the main PCB
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
Turn ON the power of the unit.
2
Measure the voltage between the wires LC‑NC on the main PCB.
Result:
The measured voltage MUST be 230 V AC.
3
Measure the voltage on connector X99A on the main PCB.
Result:
The measured voltage MUST be 230 V AC.
b
a
c
a
LC
b
NC
c
Connector X99A