Troubleshooting
Service manual
43
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
1
Perform a check of the low pressure switch. See
167].
Possible cause:
Faulty low pressure switch.
2
Perform a check of the main PCB. See
171].
Possible cause:
Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.44 H5-00 – Malfunction of compressor overload protection
Trigger
Effect
Reset
Compressor overload
protection is defective.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check that all stop valves of the refrigerant circuit are open. See
Possible cause:
Closed stop valve in the refrigerant circuit.
2
Check if the refrigerant circuit is clogged. See
Possible cause:
Clogged refrigerant circuit.
3
Perform a check of the compressor. See
134].
Possible cause:
Faulty compressor or miswiring of the compressor power
supply cable.
4
Check liquid back issue. Check expansion valve operation. See
Possible cause:
Expansion valve CANNOT keep minimum superheat of 3 K
while running as evaporator.
5
Check if the refrigerant circuit is correctly charged. See
Possible cause:
Refrigerant overcharge.
6
Perform a check of the 4‑way valve. See
Possible cause:
Faulty 4‑way valve.
7
Perform
a
check
of
the
discharge
pipe
thermistor.
See
248].
Possible cause:
Faulty discharge pipe thermistor or connector fault.
8
Perform a check of the main PCB. See
171].
Possible cause:
Faulty main PCB.