3
|
Components
Service manual
139
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
a
a
Compressor wire terminals cover
3
Disconnect the Faston connectors from the compressor wire terminals U, V
and W.
INFORMATION
Note the position of the Faston connectors on the compressor wire terminals to
allow correct connection during installation.
V
W
U
c
Wire terminal U
V
Wire terminal V
W
Wire terminal W
4
Set the Megger voltage to 500 V DC or 1000 V DC.
5
Measure the insulation resistance between the following terminals. The
measured insulation resistance MUST be >3 MΩ.
▪
U–ground,
▪
V–ground,
▪
W–ground.
Compressor insulation measurements
are correct?
Action
Yes
Compressor is OK. Return to
troubleshooting of the specific error
and continue with the next procedure.
No
Replace the compressor, see
Содержание ALTHERMA