4
|
Third party components
Service manual
308
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
Is the outdoor temperature within the
operating range?
Action
Yes
Return to the troubleshooting of the
specific error and continue with the
next procedure.
No
Wait for the outdoor temperature to
return within the operating range.
To check the required space around the outdoor unit heat exchanger
1
Check if the space around the outdoor unit heat exchanger is sufficient. See
the installation manual for the required space specifications. Adjust as
needed.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.