Troubleshooting
Service manual
12
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
2.3.2 7H-04 – Water flow problem during domestic hot water production
Trigger
Effect
Reset
Water flow abnormality
determined mainly during
domestic hot water.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
NOTICE
Focus the troubleshooting on the domestic hot water circuit.
1
Check that all stop valves of the water circuit are open. See
299].
Possible cause:
Closed stop valve in the water circuit.
2
Possible cause:
Air in the water circuit.
3
Possible cause:
Water flow is too low.
4
Possible cause:
Water pressure is too low.
5
Check if a by‑pass is installed in the water circuit. See
299].
Possible cause:
No by‑pass installed in the water circuit.
6
Perform an electrical check of the water flow sensor. See
Possible cause:
Faulty water flow sensor.
7
Perform a check of the 3-way valve. See
86].
Possible cause:
Faulty 3‑way valve.
8
Perform a check of the water pump. See
276].
Possible cause:
Faulty water pump.
9
Perform a check of the hydro PCB. See
Possible cause:
Faulty hydro PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.