Make sure to re‑apply insulation removed during repair.
▪
Pipe expansion / flare making:
-
Remove any burrs on the cut surface using the correct tool such as reamer or
scraper (note that excessive deburring can thin the pipe walls and cause
cracking of the pipe).
-
Make sure the flare has the correct size (use a flare gauge).
-
Make sure no particles remain in the piping.
-
Apply just a drop of refrigerant oil on the inner surface of the flare.
-
Make sure the flare connection is tightened with the correct torque (torque
values refer to installation manual).
▪
Brazing:
-
Use the correct brazing tool.
-
Use a phosphor copper filler metal (silver composition of 0 to 2%). Do not use
flux material.
-
Flush the piping before brazing with nitrogen to avoid oxidation of the inside of
the copper tubes (nitrogen purity ≥99.99%).
4.3 Water circuit
4.3.1 Checking procedures
To check for an external pump
1
Inspect the installation outside the unit and check for the presence of an
external pump. This may have an impact on the water flow inside the unit.
An external pump was found in the
installation?
Action
Yes
Remove the external pump from the
installation, see
302].
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To check the water pressure
1
Turn ON the power of the unit.
INFORMATION
Make sure that the water pressure sensor is functioning correctly.
2
Read the water pressure on the home screen of the user interface.
Result:
The pressure MUST be 1~2 bar.
Is the water pressure correct?
Action
Yes
Return to the troubleshooting of the
specific error and continue with the
next procedure.