2
|
Troubleshooting
Service manual
56
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
2.3.65 P3-00 – Abnormal direct current
Trigger
Effect
Reset
Malfunction decision by
exceeding direct current
limit value.
Unit will stop operating.
Automatic reset.
To solve the error code
1
Possible cause:
Onboard sensor error.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.66 P4-00 – Outdoor unit: Malfunction of radiating fin temperature sensor
Trigger
Effect
Reset
Radiating fin thermistor
input is out of range.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform
a
check
of
the
radiation
fin
thermistor.
See
Possible cause:
Faulty radiation fin thermistor.
2
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.67 PJ-00 – Capacity setting mismatch
Trigger
Effect
Reset
Outdoor unit main PCB
detects a defective
capacity in EEPROM.
Unit will stop operating.
Manual reset via user
interface.
Power supply reset.
To solve the error code
1
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB.