3
|
Components
Service manual
113
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
a
a
a
a
Backup heater contactor
2
Measure the backup heater resistance as shown in the table below. Tolerance
= ± 10%.
3 kW
6 kW
6 kW
9 kW
1~230 V
1~230 V
3N~400 V
3N~400 V
K1M/1
K5M/13
53 Ω
53 Ω
OL
OL
K1M/3
106 Ω
106 Ω
106 Ω
106 Ω
K1M/5
159 Ω
159 Ω
106 Ω
106 Ω
K1M/3
K1M/5
53 Ω
53 Ω
106 Ω
106 Ω
K2M/1
K5M/13
26.5 Ω
26.5 Ω
OL
OL
K2M/3
OL
OL
53 Ω
53 Ω
K2M/5
OL
OL
53 Ω
53 Ω
K2M/3
K2M/5
53 Ω
53 Ω
53 Ω
53 Ω
K1M/5
K2M/1
132.5 Ω
132.5 Ω
OL
OL
INFORMATION
314] for more detailed information.
Is the measured backup heater
resistance correct?
Action
Yes
Return to
112] of the backup
heater and continue with the next
procedure.
No
Replace the backup heater, see
117].