Components
Service manual
137
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
V
W
U
c
Wire terminal U
V
Wire terminal V
W
Wire terminal W
CAUTION
Before measuring the compressor motor windings resistance, measure the
resistance of the multimeter probes by holding the probes against each other. If the
measured resistance is NOT 0 Ώ, this value MUST be substracted from the measured
winding resistance.
4
Measure the resistance between the compressor motor windings U-V, V-W
and U-W.
Result:
All measurements MUST be approximately the same.
Unit
Compressor
Winding resistance value
(at temperature of 20°C)
Single phase unit
M1C
0.343 Ω ± 5%
Three phase unit
M1C
1.16 Ω ± 5%
Compressor motor winding
measurements are correct?
Action
Yes
Continue with the next step.
No
Replace the compressor, see
140].
5
Measure the continuity of the U, V and W wires between the compressor and
the PCB. If no continuity, correct as needed, see
6
Connect the Faston connectors to the compressor wire terminals U, V and W