2
|
Troubleshooting
Service manual
84
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
Root cause category: parameter (setting)
Possible failure
Root cause
Check
Repair
Displayed date/time is
wrong - schedules NOT
correctly executed.
▪
NOT set date/time after
initial start-up,
▪
No power supply for
more than 48 hours.
Set date/time according to
operation manual
instructions.
Set date/time according to
operation manual
instructions.
Displayed date/time is
wrong - schedules NOT
correctly executed.
Daylight Saving Time NOT
set correctly.
Check Daylight Saving Time
settings.
Set Daylight Saving Time
according to operation
manual.
Incorrect setting of unit
control method (setting
[C‑07]).
Incorrect setting of unit
control method (setting
[C‑07]) (leaving water
control, room thermostat
control, ext. room
thermostat control).
Check if setting [C‑07]
(leaving water control,
room thermostat control,
ext. room thermostat
control) is in set according
to the application.
Incorrect setting of space
heating OFF temperature
(setting [4‑02]).
Incorrect setting of space
heating OFF temperature
(setting [4‑02]).
Check if setting space
heating OFF temperature
(setting [4‑02]) is correct
(keep at 35°C).
Preferential kWh rate
power supply settings and
electrical connections do
NOT match.
Preferential kWh rate
power supply settings and
electrical connections do
NOT match.
Check preferential kWh
rate power supply settings
and electrical connections
(see installer reference
guide).
Root cause category: component – electrical
Possible failure
Root cause
Check
Repair
Hydro PCB NOT
operational.
▪
No power supply,
▪
Faulty transformer,
▪
Hydro PCB malfunction.
▪
Confirm that HAP led is
blinking
in
regular
intervals,
▪
Confirm power supply
towards hydro PCB,
▪
Check good operation of
transformer.
▪
Re-establish power to
hydro PCB.
Replace hydro PCB in case
power supply and
transformer are OK but led
is NOT blinking.
Outdoor unit PCB
malfunction (Main PCB,
inverter PCB, …)
▪
No power supply,
▪
Outdoor
unit
PCB
malfunction.
▪
Confirm that HAP led is
blinking
in
regular
intervals,
▪
Confirm power supply
towards outdoor unit
PCB,
▪
Check good operation of
outdoor unit PCB.
▪
Re-establish power to
outdoor unit PCB.
Replace outdoor unit PCB
in case power supply is OK
but led is NOT blinking or
in case of PCB not
operating correctly.
Reactor coil broken.
Component problem.
Check continuity of the
reactor coil.
Replace the reactor coil in
case faulty.