4
|
Third party components
Service manual
304
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To add water to the water circuit
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
230].
1
To fill the water circuit, use a field supply filling kit. Make sure you comply with
the applicable legislation.
2
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To open the stop valves of the water circuit
1
The stop valves are located outside the unit. Open the valves by placing them
in line with the piping.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To open the air purge valves of the water circuit
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
230].
1
Place the air purge valve, installed inside the unit, in the open position by
turning it clockwise.
INFORMATION
If a backup heater kit is installed, place the air purge valve of the backup heater kit in
the open position.