EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
INFORMATION
If you have a multimeter with data logging functionality, record the current in 1 of
the U‑V‑W wires at compressor start‑up. If mechanical lock is present, logged current
will drastically increase to a peak value and the unit will trigger an error.
INFORMATION
If a mechanical lock is present, also check and eliminate the root cause. Mechanical
lock is most likely caused by lack of lubrication (which might be related to overheat
or wet operation), failing crankcase heater (if available), impurities in the refrigerant,
….
A mechanical lock is present on the
compressor?
Action
Yes
Replace the compressor, see
No
Perform an mechanical check of the
compressor, see
134].
To perform a mechanical check of the compressor
Prerequisite:
First perform an auditive check of the compressor, see
Prerequisite:
Stop the unit operation via the user interface.
1
Turn OFF the respective circuit breaker.
2
Visually check:
▪
For oil drops around the compressor. Locate and fix as needed.
▪
Pipes for signs of damage. Replace pipes as needed.
3
Check that the compressor bolts are correctly fixed. Fix as needed.
4
Check that the compressor wire terminals cover is correctly installed and
fixed. Correct as needed.
5
Check the compressor dampers for any damage.
a
a
1
Damper