2
|
Troubleshooting
Service manual
66
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check for improper combination of the indoor unit and the water tank. See
the combination table in the Databook for more information.
2
Check the setting [E‑05] and [E‑07] via the user interface. See
266].
Possible cause:
Faulty [E‑05] or [E‑07] setting.
3
Perform a check of the hydro PCB. See
Possible cause:
Faulty hydro PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.83 UF-00 – Reversed piping or bad communication wiring detection
Trigger
Effect
Reset
Reversed piping or bad
communication, wiring
detection.
Unit will NOT start
operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check that all stop valves of the refrigerant circuit are open. See
286].
Possible cause:
Closed stop valve in the refrigerant circuit.
2
Check that the piping and wiring connections of the system are correctly
installed. See
331] and
Possible cause:
Piping and/or wiring mismatch.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.