Components
Service manual
217
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
a
b
a
Fuse F1U
b
Fuse F3U
Is the problem solved?
Action
Yes
No further actions required.
No
Return to
204] of the noise filter
PCB and continue with the next
procedure.
3.16 Outdoor unit fan motor
3.16.1 Single phase outdoor unit
Checking procedures
INFORMATION
It is recommended to perform the checks in the listed order.
To perform a mechanical check of the propeller fan blade assembly
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
If propeller fan blade touches the bellmounth, check if the fan motor is
correctly mounted on its base, see
2
Check the state of the propeller fan blade assembly for damage, deformations
and cracks.