To prevent electrical hazards
To check the rectifier voltage
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
1
Do NOT open the electrical component box cover for 10 minutes after turning
off the power supply.
2
Remove the required plate work, see
DANGER: RISK OF ELECTROCUTION
Do NOT touch any live parts or PCB's.
3
Measure the voltage between terminals on the terminal block for power
supply with a tester and confirm that the power supply is shut off. In addition,
measure points as shown in the figure, with a tester and confirm that the
voltage of the capacitor in the main circuit is less than 10 V DC.
C+
C-
C+
C-
A
B
A
3‑phase unit
B
1‑phase unit
DANGER: RISK OF ELECTROCUTION
Confirm the rectifier voltage is below 10 V DC before proceeding.
To check the wiring between the outdoor unit and domestic hot water tank
1
Check that all wires are properly connected and that all connectors are fully
plugged‑in.
2
Check that no connectors or wires are damaged.
3
Check that the wiring corresponds with the wiring diagram, see
INFORMATION
Correct the wiring as needed.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.