CPI Canada Inc.
Installation
2
Indico 100 Series Service Manual Ch # 740895-04 Rev. H
Page 2-26
2.13.3 Dual Speed Starter Tube Select Table (cont)
THE DUAL SPEED STARTER USES MODULATION STRATEGIES TO OBTAIN THE DESIRED OUTPUTS. MEASURED VOLTAGES MAY NOT AGREE
WITH THOSE LISTED IN THE TABLE. HOWEVER, THE CURRENTS FLOWING IN THE STATOR WINDINGS ARE EQUIVALENT TO THOSE THAT WOULD
EXIST IF THE STATOR WAS EXCITED WITH THESE VOLTAGES.
NOTE 1:
Tube types designated as low speed only or high speed only must be programmed for low speed only or high speed only operation.
Refer to chapter 3, section 3C.5.1 for details.
*
Dual speed starter part numbers 733317-XX are used in 400 VAC 3
φ
generators and in 480 VAC 3
φ
generators with a line adjusting transformer.
Dual speed starter part numbers 735925-XX are used in 230 VAC 1
φ
generators and in 480 VAC 3
φ
direct input generators (using no line
adjusting transformer).