20-12
Cisco ONS 15454 SDH Procedure Guide, R7.0
78-17194-01
Chapter 20 DLPs D300 to D399
DLP- D324 Install Alarm Cables on the MIC-A/P
Figure 20-4
Removing the ONS 15454 SDH FMEC Cover
Step 4
Detach the cover from the pin of the hinge.
Step 5
Remove the cover carefully from the left pin of the hinge.
Step 6
Return to your originating procedure (NTP).
DLP-D324 Install Alarm Cables on the MIC-A/P
Step 1
Using 0.51 mm² or 0.64 mm² (#22 or #24 AWG) wires, connect the alarm and control wires on the
appropriate pins of the DB-62 connector. The pin connectors, signal names, and functions are listed in
Purpose
This task installs alarm cables on the MIC-A/P FMEC so that you can
provision external (environmental) alarms and controls with the AIC-I
card.
Tools/Equipment
DB-62 connector
0.51 mm² or 0.64 mm² (#22 or #24 AWG) wires
Prerequisite Procedures
NTP-D220 Install the Power and Signal FMECs, page 1-7
Required/As Needed
As needed
Onsite/Remote
Onsite
Security Level
None
71087
FAN
FAIL
CRIT
MAJ
MIN
Pin hinge
FMEC cover
Hinge-locking
spring
Содержание ONS 15454 SDH
Страница 26: ...Tables vi Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 ...
Страница 62: ...xxii Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 About this Guide ...
Страница 64: ...xxiv Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 About this Guide ...
Страница 66: ...xxvi Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 About this Guide ...
Страница 414: ...16 4 Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 Chapter 16 Power Down the Node NTP D114 Power Down the Node ...
Страница 832: ...A 14 Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 Appendix A CTC Information and Shortcuts Equipment Inventory ...
Страница 860: ...Index IN 28 Cisco ONS 15454 SDH Procedure Guide R6 0 78 17194 01 ...