5-24
Cisco ONS 15454 SDH Procedure Guide, R7.0
78-17194-01
Chapter 5 Turn Up a Network
NTP- D343 SNCP Acceptance Test
NTP-D343 SNCP Acceptance Test
Step 1
Complete the
“DLP-D60 Log into CTC” task on page 17-49
at one of the ONS 15454 SDHs on the
SNCP you are testing. If you are already logged in, continue with Step 2.
Step 2
From the View menu, choose
Go to Network View
.
Step 3
Click the
Alarms
tab.
a.
Verify that the alarm filter is not on. See the
“DLP-D227 Disable Alarm Filtering” task on
as necessary.
b.
Verify that no unexplained alarms appear on the network. If unexplained alarms appear, resolve
them before continuing. Refer to the
Cisco ONS 15454 SDH Troubleshooting Guide
if necessary
.
c.
Complete the
“DLP-D147 Export CTC Data” task on page 18-38
to export alarm information.
Step 4
Click the
Conditions
tab.
a.
Verify that no unexplained conditions appear on the network. If unexplained conditions appear,
resolve them before continuing. Refer to the
Cisco ONS 15454 SDH Troubleshooting Guide
if
necessary.
b.
Complete the
“DLP-D147 Export CTC Data” task on page 18-38
to export conditions information.
Step 5
On the network map, double-click the node that you logged into in Step
.
Step 6
Create a test circuit from that node to the next adjacent SNCP node.
•
For VC4 circuits, complete the
“NTP-D323 Create an Automatically Routed High-Order Circuit”
. When you set the circuit state, choose
Unlocked
and check the
Apply to drop ports
check box.
•
For VC3 circuits, complete the
“NTP-D54 Create an Automatically Routed Low-Order VC3
Circuit” procedure on page 6-31
. When you set the circuit state, choose
Unlocked
and check the
Apply to drop ports
check box.
•
For VC12 circuits, complete the
“NTP-D81 Create an Automatically Routed Low-Order VC12
Circuit” procedure on page 6-19
. When you set the circuit state, choose
Unlocked
and check the
Apply to drop ports
check box.
•
For VC11 circuits, complete the
“NTP-D334 Create an Automatically Routed Low-Order VC11
Circuit” procedure on page 6-7
. When you set the circuit state, choose
Unlocked
and check the
Apply to drop ports
check box.
Step 7
Configure the test set for the test circuit type you created:
•
VC4 or VC4-nc—If you are testing a VC4 circuit or a VC4-nc circuit on an STM-N card, you must
have a direct optical interface into the ONS 15454 SDH. Set the test set for STM-N. For information
about configuring your test set, consult your test set user guide.
Purpose
This procedure tests an SNCP ring.
Tools/Equipment
Test set and cables appropriate to the test circuit you will create.
Prerequisite Procedures
NTP-D44 Provision SNCP Nodes, page 5-22
Required/As Needed
As needed
Onsite/Remote
Onsite
Security Level
Provisioning or higher
Содержание ONS 15454 SDH
Страница 26: ...Tables vi Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 ...
Страница 62: ...xxii Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 About this Guide ...
Страница 64: ...xxiv Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 About this Guide ...
Страница 66: ...xxvi Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 About this Guide ...
Страница 414: ...16 4 Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 Chapter 16 Power Down the Node NTP D114 Power Down the Node ...
Страница 832: ...A 14 Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 Appendix A CTC Information and Shortcuts Equipment Inventory ...
Страница 860: ...Index IN 28 Cisco ONS 15454 SDH Procedure Guide R6 0 78 17194 01 ...