Section 10. Troubleshooting
518
If power supply components are working properly and the system has peripherals
with high current drain, such as a satellite transmitter, verify that the power supply
is designed to provide adequate power. Information on power supplies available
from Campbell Scientific can be obtained at www.campbellsci.com. Basic
information is available in Power Supplies — List
10.9.2 Troubleshooting Power Supplies — Examples
Symptom:
o
CRBasic program does not execute.
o
Low12VCount of the Status table displays a large number.
Possible affected equipment:
o
Batteries
o
Charger/regulators
o
Solar panels
o
Transformers
Likely causes:
o
Batteries may need to be replaced or recharged.
o
Charger/regulators may need to be fixed or re-calibrated.
o
Solar panels or transformers may need to be fixed or replaced.
10.9.3 Troubleshooting Power Supplies — Procedures
Required Equipment:
o
Voltmeter
o
5 kΩ resistor
o
50 Ω, 1 watt resistor for the charging circuit tests and to adjust
the
charging circuit voltage.
10.9.3.1 Battery Test
The procedure outlined in this flow chart tests sealed-rechargeable or alkaline
batteries in the PS100 charging regulator, or a sealed-rechargeable battery
attached to a CH100 charging regulator. If a need for repair is indicated after
following the procedure, see Assistance
(p. 5)
for information on sending items to
Campbell Scientific.
Содержание CR3000 Micrologger
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 6: ......
Страница 30: ......
Страница 34: ......
Страница 36: ......
Страница 96: ......
Страница 200: ...Section 7 Installation 200 FIGURE 42 Running Average Frequency Response FIGURE 43 Running Average Signal Attenuation ...
Страница 485: ...Section 8 Operation 485 8 11 2 Data Display FIGURE 110 Keyboard and Display Displaying Data ...
Страница 487: ...Section 8 Operation 487 FIGURE 112 CR1000KD Real Time Custom ...
Страница 488: ...Section 8 Operation 488 8 11 2 3 Final Storage Data FIGURE 113 Keyboard and Display Final Storage Data ...
Страница 489: ...Section 8 Operation 489 8 11 3 Run Stop Program FIGURE 114 Keyboard and Display Run Stop Program ...
Страница 491: ...Section 8 Operation 491 FIGURE 116 Keyboard and Display File Edit ...
Страница 495: ...Section 8 Operation 495 Low power standby whenever possible Low power bus sets bus and modules to low power ...
Страница 496: ......
Страница 502: ......
Страница 564: ...Section 11 Glossary 564 FIGURE 126 Relationships of Accuracy Precision and Resolution ...
Страница 566: ......
Страница 594: ......
Страница 598: ......
Страница 600: ......
Страница 602: ......
Страница 624: ......
Страница 642: ......
Страница 643: ......