Section 8. Operation
360
voltage vs. temperature curve) are needed for the various thermocouples. Lacking
this information, a reasonable approach is to apply the percentage errors, with
perhaps 0.25% added on, to the difference in temperature being measured by the
thermocouple.
Limits of Error for Thermocouple Wire (Reference Junction at 0°C)
Thermocouple
Temperature
Limits of Error
(Whichever is greater)
Type
Range °C
Standard
Special
T
–200 to 0
± 1.0 °C or 1.5%
0 to 350
± 1.0 °C or 0.75%
± 0.5 °C or 0.4%
J
0 to 750
± 2.2 °C or 0.75%
± 1.1 °C or 0.4%
E
–200 to 0
± 1.7 °C or 1.0%
0 to 900
± 1.7 °C or 0.5%
± 1.0 °C or 0.4%
K
–200 to 0
± 2.2 °C or 2.0%
0 to 1250
± 2.2 °C or 0.75%
± 1.1 °C or 0.4%
R or S
0 to 1450
± 1.5 °C or 0.25%
± 0.6 °C or 0.1%
B
800 to 1700
± 0.5%
Not Established.
Thermocouple Voltage Measurement Error
Thermocouple outputs are extremely small — 10 to 70 µV per °C. Unless high
resolution input ranges are used when programming, the CR3000, accuracy and
sensitivity are compromised. Table Voltage Range for Maximum Thermocouple
Resolution
(p. 360)
lists high resolution ranges available for various thermocouple
types and temperature ranges. The following four example calculations of
thermocouple input error demonstrate how the selected input voltage range
impacts the accuracy of measurements. Figure Input Error Calculation
(p. 361)
shows from where various values are drawn to complete the calculations. See
Measurement Accuracy
for more information on measurement accuracy and
accuracy calculations.
When the thermocouple measurement junction is in electrical contact with the
object being measured (or has the possibility of making contact) a differential
measurement should be made to avoid ground looping.
Содержание CR3000 Micrologger
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 6: ......
Страница 30: ......
Страница 34: ......
Страница 36: ......
Страница 96: ......
Страница 200: ...Section 7 Installation 200 FIGURE 42 Running Average Frequency Response FIGURE 43 Running Average Signal Attenuation ...
Страница 485: ...Section 8 Operation 485 8 11 2 Data Display FIGURE 110 Keyboard and Display Displaying Data ...
Страница 487: ...Section 8 Operation 487 FIGURE 112 CR1000KD Real Time Custom ...
Страница 488: ...Section 8 Operation 488 8 11 2 3 Final Storage Data FIGURE 113 Keyboard and Display Final Storage Data ...
Страница 489: ...Section 8 Operation 489 8 11 3 Run Stop Program FIGURE 114 Keyboard and Display Run Stop Program ...
Страница 491: ...Section 8 Operation 491 FIGURE 116 Keyboard and Display File Edit ...
Страница 495: ...Section 8 Operation 495 Low power standby whenever possible Low power bus sets bus and modules to low power ...
Страница 496: ......
Страница 502: ......
Страница 564: ...Section 11 Glossary 564 FIGURE 126 Relationships of Accuracy Precision and Resolution ...
Страница 566: ......
Страница 594: ......
Страница 598: ......
Страница 600: ......
Страница 602: ......
Страница 624: ......
Страница 642: ......
Страница 643: ......