Section 8. Operation
343
FIGURE 80: Input voltage rise and transient decay
CRBasic Measurement Settling Times
SettlingTime
Argument
Integ
Argument
Resultant
Settling Time
1
0
250
200 µs
0
_50Hz
3 ms
0
_60Hz
3 ms
integer ≥
100
integer
μs entered in
SettlingTime
argument
1
200 µs is the minimum settling time required to meet CR3000 resolution
specifications.
Settling Errors
When sensors require long lead lengths, use the following general practices to
minimize settling errors:
•
Do not use wire with PVC-insulated conductors. PVC has a high
dielectric constant, which extends input settling time.
•
Where possible, run excitation leads and signal leads in separate shields
to minimize transients.
When measurement speed is not a prime consideration, additional time can be
used to ensure ample settling time. The settling time required can be measured
with the CR3000.
•
When relatively large resistances are measured (> 1000 ohms), or
relatively long cable lengths are used (> 50 feet) with sensors requiring
current excitation, a 0.1 µf feed-forward capacitor should be placed
between the IX and IXR to prevent excessive ringing
(p. 553).
With this
capacitor present, a minimum of 3 ms is recommended for the
SettlingTime parameter in the measurement instruction. The capacitor
Содержание CR3000 Micrologger
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 6: ......
Страница 30: ......
Страница 34: ......
Страница 36: ......
Страница 96: ......
Страница 200: ...Section 7 Installation 200 FIGURE 42 Running Average Frequency Response FIGURE 43 Running Average Signal Attenuation ...
Страница 485: ...Section 8 Operation 485 8 11 2 Data Display FIGURE 110 Keyboard and Display Displaying Data ...
Страница 487: ...Section 8 Operation 487 FIGURE 112 CR1000KD Real Time Custom ...
Страница 488: ...Section 8 Operation 488 8 11 2 3 Final Storage Data FIGURE 113 Keyboard and Display Final Storage Data ...
Страница 489: ...Section 8 Operation 489 8 11 3 Run Stop Program FIGURE 114 Keyboard and Display Run Stop Program ...
Страница 491: ...Section 8 Operation 491 FIGURE 116 Keyboard and Display File Edit ...
Страница 495: ...Section 8 Operation 495 Low power standby whenever possible Low power bus sets bus and modules to low power ...
Страница 496: ......
Страница 502: ......
Страница 564: ...Section 11 Glossary 564 FIGURE 126 Relationships of Accuracy Precision and Resolution ...
Страница 566: ......
Страница 594: ......
Страница 598: ......
Страница 600: ......
Страница 602: ......
Страница 624: ......
Страница 642: ......
Страница 643: ......