Section 8. Operation
408
Measurements include the following:
•
Counts
•
Frequency (Hz)
•
Running average
Rotating magnetic-pickup sensors commonly generate ac voltage ranging from
thousandths of volts at low-rotational speeds to several volts at high-rotational
speeds. Terminals configured for low-level ac input have in-line signal
conditioning for measuring signals ranging from 20 mV RMS (
±
28 mV peak-to-
peak) to 14 V RMS (
±
20 V peak-to-peak).
P Terminals
•
Maximum input frequency is dependent on input voltage:
o
1.0 to 20 Hz at 20 mV RMS
o
0.5 to 200 Hz at 200 mV RMS
o
0.3 to 10 kHz at 2000 mV RMS
o
0.3 to 20 kHz at 5000 mV RMS
•
CRBasic instruction: PulseCount()
Internal ac coupling is used to eliminate dc-offset voltages of up to
±
0.5 Vdc.
C Terminals
Low-level ac signals cannot be measured directly by C terminals. Refer to Pulse
Input Modules — List
(p. 604)
for information on peripheral terminal expansion
modules available for converting low-level ac signals to square-wave signals.
8.1.3.3 High-Frequency Measurements
High-frequency (square-wave) signals can be measured on P or C terminals.
Common sensors that output high-frequency include:
•
Photo-chopper anemometers
•
Flow meters
Measurements include counts, frequency in hertz, and running average. Refer to
the section Frequency Resolution
(p. 409)
for information about how the resolution
of a frequency measurement can be different depending on whether the
measurement is made with the PulseCount() or TimerIO() instruction.
Содержание CR3000 Micrologger
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 6: ......
Страница 30: ......
Страница 34: ......
Страница 36: ......
Страница 96: ......
Страница 200: ...Section 7 Installation 200 FIGURE 42 Running Average Frequency Response FIGURE 43 Running Average Signal Attenuation ...
Страница 485: ...Section 8 Operation 485 8 11 2 Data Display FIGURE 110 Keyboard and Display Displaying Data ...
Страница 487: ...Section 8 Operation 487 FIGURE 112 CR1000KD Real Time Custom ...
Страница 488: ...Section 8 Operation 488 8 11 2 3 Final Storage Data FIGURE 113 Keyboard and Display Final Storage Data ...
Страница 489: ...Section 8 Operation 489 8 11 3 Run Stop Program FIGURE 114 Keyboard and Display Run Stop Program ...
Страница 491: ...Section 8 Operation 491 FIGURE 116 Keyboard and Display File Edit ...
Страница 495: ...Section 8 Operation 495 Low power standby whenever possible Low power bus sets bus and modules to low power ...
Страница 496: ......
Страница 502: ......
Страница 564: ...Section 11 Glossary 564 FIGURE 126 Relationships of Accuracy Precision and Resolution ...
Страница 566: ......
Страница 594: ......
Страница 598: ......
Страница 600: ......
Страница 602: ......
Страница 624: ......
Страница 642: ......
Страница 643: ......