Section 10. Troubleshooting
516
•
Check for condensation, which can sometimes cause leakage from a 12
Vdc source terminal into other places.
•
Check for a lose ground wire on a sensor powered from a 12V or SW12
terminal.
•
If a multimeter is not available, disconnect sensors, one at a time, that
require power from 9 to 16 Vdc. If measurements return to normal, you
have found the cause.
10.8
Troubleshooting — Communications
10.8.1 RS-232
With newer system, USB enumeration can be a big problem. For example, if
your PC is supporting three external screens, a keyboard, a mouse, and other USB
connections, such as your datalogger connection, on a USB expansion box, the set
up is rife with potential for enumeration mishaps. The best way to resolve a USB
problem with a datalogger connection is to remove as many USB devices as
possible, completely power down the system (disconnect the system from AC
power and UPS devices, then power the system back up, then connect the
datalogger, check that it is working with the support software, then reconnect all
other devices one by one.
On system using nine-pin serial connections, a simple way to test a PC serial port
is to physically connect pin 2 on the serial port with pin 3. This connects the
transmit to the receive. Using a terminal emulator, you should be able to type a
character on the PC keyboard and have it show up on the terminal emulator
screen. If it does not show up, you either have the wrong com port selected in the
terminal emulator set up, or there may be some other program commandeering the
serial port.
Baud rate mis-match between the CR3000 and datalogger support software
(p. 90)
is often the cause of communication problems. By default, CR3000 baud rate
auto-adjusts to match that of the software. However, settings changed in the
CR3000 to accommodate a specific RS-232 device, such as a smart sensor,
display or modem, may confine the RS-232 port to a single baud rate. If the baud
rate can be guessed at and entered into support software parameters,
communications may be established. Once communications are established,
CR3000 baud rate settings can be changed. Clues as to what the baud rate may
be set at can be found by analyzing current and previous CR3000 programs for
the SerialOpen() instruction, since SerialOpen() specifies a baud rate.
Documentation provided by the manufacturer of the previous RS-232 device may
also hint at the baud rate.
10.8.2 Communicating with Multiple PCs
The CR3000 can communicate with multiple PCs simultaneously. For example,
the CR3000 may be a node of an internet PakBus network communicating with a
distant instance of LoggerNet. An onsite technician can communicate with the
CR3000 using PC200W with a serial connection, so long as the PakBus addresses
Содержание CR3000 Micrologger
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 6: ......
Страница 30: ......
Страница 34: ......
Страница 36: ......
Страница 96: ......
Страница 200: ...Section 7 Installation 200 FIGURE 42 Running Average Frequency Response FIGURE 43 Running Average Signal Attenuation ...
Страница 485: ...Section 8 Operation 485 8 11 2 Data Display FIGURE 110 Keyboard and Display Displaying Data ...
Страница 487: ...Section 8 Operation 487 FIGURE 112 CR1000KD Real Time Custom ...
Страница 488: ...Section 8 Operation 488 8 11 2 3 Final Storage Data FIGURE 113 Keyboard and Display Final Storage Data ...
Страница 489: ...Section 8 Operation 489 8 11 3 Run Stop Program FIGURE 114 Keyboard and Display Run Stop Program ...
Страница 491: ...Section 8 Operation 491 FIGURE 116 Keyboard and Display File Edit ...
Страница 495: ...Section 8 Operation 495 Low power standby whenever possible Low power bus sets bus and modules to low power ...
Страница 496: ......
Страница 502: ......
Страница 564: ...Section 11 Glossary 564 FIGURE 126 Relationships of Accuracy Precision and Resolution ...
Страница 566: ......
Страница 594: ......
Страница 598: ......
Страница 600: ......
Страница 602: ......
Страница 624: ......
Страница 642: ......
Страница 643: ......