Section 7. Installation
191
Program Signatures
'This program example demonstrates how to request the program text signature (ProgSig =
Status.ProgSignature), and the
'binary run-time signature (RunSig = Status.RunSignature). It also calculates two
'executable code segment signatures (ExeSig(1), ExeSig(2))
'Define Public Variables
Public
RunSig, ProgSig, ExeSig(2),x,y
'Define Data Table
DataTable
(Signatures,1,1000)
DataInterval
(0,1,Day,10)
Sample
(1,ProgSig,FP2)
Sample
(1,RunSig,FP2)
Sample
(2,ExeSig(),FP2)
EndTable
'Program
BeginProg
ExeSig() =
Signature
'initialize executable code signature
'function
Scan
(1,Sec,0,0)
ProgSig = Status.ProgSignature
'Set variable to Status table entry
'"ProgSignature"
RunSig = Status.RunSignature
'Set variable to Status table entry
'"RunSignature"
x = 24
ExeSig(1) = Signature
'signature includes code since initial
'Signature instruction
y = 43
ExeSig(2) = Signature
'Signature includes all code since
'ExeSig(1) = Signature
CallTable
Signatures
NextScan
7.7.1.8 Use of Multiple Scans
CRBasic example Use of Multiple Scans
(p. 191)
shows how to use of multiple
scans. Some applications require measurements or processing to occur at an
interval different from that of the main program scan. Secondary, or slow
sequence, scans are prefaced with the SlowSequence instruction.
Содержание CR3000 Micrologger
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 6: ......
Страница 30: ......
Страница 34: ......
Страница 36: ......
Страница 96: ......
Страница 200: ...Section 7 Installation 200 FIGURE 42 Running Average Frequency Response FIGURE 43 Running Average Signal Attenuation ...
Страница 485: ...Section 8 Operation 485 8 11 2 Data Display FIGURE 110 Keyboard and Display Displaying Data ...
Страница 487: ...Section 8 Operation 487 FIGURE 112 CR1000KD Real Time Custom ...
Страница 488: ...Section 8 Operation 488 8 11 2 3 Final Storage Data FIGURE 113 Keyboard and Display Final Storage Data ...
Страница 489: ...Section 8 Operation 489 8 11 3 Run Stop Program FIGURE 114 Keyboard and Display Run Stop Program ...
Страница 491: ...Section 8 Operation 491 FIGURE 116 Keyboard and Display File Edit ...
Страница 495: ...Section 8 Operation 495 Low power standby whenever possible Low power bus sets bus and modules to low power ...
Страница 496: ......
Страница 502: ......
Страница 564: ...Section 11 Glossary 564 FIGURE 126 Relationships of Accuracy Precision and Resolution ...
Страница 566: ......
Страница 594: ......
Страница 598: ......
Страница 600: ......
Страница 602: ......
Страница 624: ......
Страница 642: ......
Страница 643: ......