Section 7. Installation
184
Groundwater Pump Test
'This program example demonstrates the use of multiple scans in a program by running a
'groundwater pump test. Note that Scan() time units of Sec have been changed to mSec for
'this demonstration to allow the program to run its course in a short time. To use this
'program for an actual pump test, change the Scan() instruction mSec arguments to Sec. You
'will also need to put a level measurement in the MeasureLevel subroutine.
'A groundwater pump test requires that water level be measured and recorded
'according to the following schedule:
'Minutes into Test Data-Output Interval
'----------------- --------------------
' 0-10 10 seconds
' 10-30 30 seconds
' 30-100 60 seconds
' 100-300 120 seconds
' 300-1000 300 seconds
' 1000+ 600 seconds
'Declare Variables
Public
PTemp
Public
Batt_Volt
Public
Level
Public
LevelMeasureCount
As Long
Public
ScanCounter(6)
As Long
'Declare Data Table
DataTable
(LogTable,1,-1)
Minimum
(1,Batt_Volt,FP2,0,False)
Sample
(1,PTemp,FP2)
Sample
(1,Level,FP2)
EndTable
'Declare Level Measurement Subroutine
Sub
MeasureLevel
LevelMeasureCount = LevelMeasur 1
'Included to show passes through sub-routine
'Level measurement instructions goes here
EndSub
'Main Program
BeginProg
'Minute 0 to 10 of test: 10-second data-output interval
Scan
(10,mSec,0,60)
'There are 60 10-second scans in 10 minutes
ScanCounter(1) = ScanCounter(1) + 1
'Included to show passes through this scan
Battery
(Batt_volt)
PanelTemp
(PTemp,250)
Call
MeasureLevel
'Call Output Tables
CallTable
LogTable
NextScan
Содержание CR3000 Micrologger
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 6: ......
Страница 30: ......
Страница 34: ......
Страница 36: ......
Страница 96: ......
Страница 200: ...Section 7 Installation 200 FIGURE 42 Running Average Frequency Response FIGURE 43 Running Average Signal Attenuation ...
Страница 485: ...Section 8 Operation 485 8 11 2 Data Display FIGURE 110 Keyboard and Display Displaying Data ...
Страница 487: ...Section 8 Operation 487 FIGURE 112 CR1000KD Real Time Custom ...
Страница 488: ...Section 8 Operation 488 8 11 2 3 Final Storage Data FIGURE 113 Keyboard and Display Final Storage Data ...
Страница 489: ...Section 8 Operation 489 8 11 3 Run Stop Program FIGURE 114 Keyboard and Display Run Stop Program ...
Страница 491: ...Section 8 Operation 491 FIGURE 116 Keyboard and Display File Edit ...
Страница 495: ...Section 8 Operation 495 Low power standby whenever possible Low power bus sets bus and modules to low power ...
Страница 496: ......
Страница 502: ......
Страница 564: ...Section 11 Glossary 564 FIGURE 126 Relationships of Accuracy Precision and Resolution ...
Страница 566: ......
Страница 594: ......
Страница 598: ......
Страница 600: ......
Страница 602: ......
Страница 624: ......
Страница 642: ......
Страница 643: ......