Section 7. Installation
197
Array Assigned Expression: Fill Array Dimension
'Example: Fill Array Dimension
Public
A(3)
Public
B(3,2)
Public
C(4,3,2)
Public
Da(3,2) = {1,1,1,1,1,1}
Public
Db(3,2)
Public
DMultiplier(3) = {10,100,1000}
Public
DOffset(3) = {1,2,3}
BeginProg
Scan
(1,Sec,0,0)
A() = 1
'set all elements of 1D array or first dimension to 1
B(1,1)() = 100
'set B(1,1) and B(1,2) to 100
B(-2,1)() = 200
'set B(2,1) and B(3,1) to 200
B(-2,2)() = 300
'set B(2,2) and B(3,2) to 300
C(1,-1,1)() = A()
'copy A(1), A(2), and A(3) into C(1,1,1), C(1,2,1), and C(1,3,1),
'respectively
C(2,-1,1)() = A() * 1.8 + 32
'scale and then copy A(1), A(2), and A(3) into C(2,1,1),
'C(2,2,1), and C(2,3,1), respectively
'scale the first column of Da by corresponding multiplier and offset
'copy the result into the first column of Db
'then set second column of Db to NAN
Db(-1,1)() = Da(-1,1)() * DMultiplier() + DOffset()
Db(-1,2)() = NAN
NextScan
EndProg
7.7.4 Data Output: Calculating Running Average
The AvgRun() instruction calculates a running average of a measurement or
calculated value. A running average (Dest) is the average of the last N values
where N is the number of values, as expressed in the running-average equation:
where X
N
is the most recent value of the source variable and X
N-1
is the previous
value (X
1
is the oldest value included in the average, i.e., N-1 values back from
the most recent). NANs are ignored in the processing of AvgRun() unless all
values in the population are NAN.
AvgRun() uses high-precision math, so a 32-bit extension of the mantissa is saved
and used internally resulting in 56 bits of precision.
Содержание CR3000 Micrologger
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 6: ......
Страница 30: ......
Страница 34: ......
Страница 36: ......
Страница 96: ......
Страница 200: ...Section 7 Installation 200 FIGURE 42 Running Average Frequency Response FIGURE 43 Running Average Signal Attenuation ...
Страница 485: ...Section 8 Operation 485 8 11 2 Data Display FIGURE 110 Keyboard and Display Displaying Data ...
Страница 487: ...Section 8 Operation 487 FIGURE 112 CR1000KD Real Time Custom ...
Страница 488: ...Section 8 Operation 488 8 11 2 3 Final Storage Data FIGURE 113 Keyboard and Display Final Storage Data ...
Страница 489: ...Section 8 Operation 489 8 11 3 Run Stop Program FIGURE 114 Keyboard and Display Run Stop Program ...
Страница 491: ...Section 8 Operation 491 FIGURE 116 Keyboard and Display File Edit ...
Страница 495: ...Section 8 Operation 495 Low power standby whenever possible Low power bus sets bus and modules to low power ...
Страница 496: ......
Страница 502: ......
Страница 564: ...Section 11 Glossary 564 FIGURE 126 Relationships of Accuracy Precision and Resolution ...
Страница 566: ......
Страница 594: ......
Страница 598: ......
Страница 600: ......
Страница 602: ......
Страница 624: ......
Страница 642: ......
Страница 643: ......