Description
Symbol
Unit
Value
Derating vs. ambient temperature:
The performance data are reduced by the
factor F
Ta
in the ambient temperature range
T
a_work_red
:
F
Ta
= 1 - [(T
a
- 40) × f
Ta
]
Using a KCU drive connection box reduces the
rated power (P
out
) at the 42 V control voltage
output. The rated power at the power section
output (P
DC_cont
) is not reduced.
T
a_work_red
°C
40 … 55
f
Ta
%/K
2.0
Derating vs. installation altitude:
At an installation altitude h > h
nenn
, the available
performance data are reduced by the factor f
2)
.
At an installation altitude in the range
h
max_ohne
to h
max
, an isolating transformer has to
be installed at the drive system mains
connection.
Operation above h
max
is not allowed!
h
max_ohne
m
2000
h
max
m
4000
Simultaneous derating for ambient temperature
and installation altitude
Allowed;
reduce performance data with the product f × F
Ta
Relative humidity
-
%
5 … 95
Absolute humidity
-
g/m
3
1 … 29
Climatic category (IEC 60721-3-3)
-
-
3K3
Allowed pollution degree (EN 50178)
-
-
2
Resistance to chemically active substances
(IEC 60721-3-3)
-
-
Class 3C1
Vibration sine: amplitude (peak-peak) at
10 … 57 Hz
1)
-
mm
0.15
Vibration sine: acceleration at 57 … 150 Hz
1)
-
g
1
Overvoltage category
-
-
III (according to IEC 60664-1)
1)
According to EN 60068-2-6
2)
Reduced performance data for drive controllers: allowed DC
bus continuous power, braking resistor continuous power, con‐
tinuous current; additionally for HCS01, HCQ, HCT drive con‐
trollers: allowed mains voltage
3)
Some components can be operated in mounting positions oth‐
er than G1. The allowed mounting positions are specified in the
technical data of the components.
Tab. 4-8:
Ambient and operating conditions (HCS, HMV, HMS, HMD, HCQ,
HCT, KCU, HLC, HNF)
IndraDrive Mi Drive Systems with KCU02, KSM02,
KMS02/03, KMV03, KNK03, KLC03
51/407
General data and specifications
R911335703_Edition 04 Bosch Rexroth AG
Содержание Rexroth IndraDrive Mi KCU02
Страница 272: ...258 407 IndraDrive Mi Drive Systems with KCU02 KSM02 KMS02 03 KMV03 KNK03 KLC03 Bosch Rexroth AG R911335703_Edition 04 ...
Страница 290: ...276 407 IndraDrive Mi Drive Systems with KCU02 KSM02 KMS02 03 KMV03 KNK03 KLC03 Bosch Rexroth AG R911335703_Edition 04 ...
Страница 312: ...298 407 IndraDrive Mi Drive Systems with KCU02 KSM02 KMS02 03 KMV03 KNK03 KLC03 Bosch Rexroth AG R911335703_Edition 04 ...
Страница 378: ...364 407 IndraDrive Mi Drive Systems with KCU02 KSM02 KMS02 03 KMV03 KNK03 KLC03 Bosch Rexroth AG R911335703_Edition 04 ...
Страница 382: ...368 407 IndraDrive Mi Drive Systems with KCU02 KSM02 KMS02 03 KMV03 KNK03 KLC03 Bosch Rexroth AG R911335703_Edition 04 ...
Страница 408: ...394 407 IndraDrive Mi Drive Systems with KCU02 KSM02 KMS02 03 KMV03 KNK03 KLC03 Bosch Rexroth AG R911335703_Edition 04 ...
Страница 420: ...Notes 406 407 IndraDrive Mi Drive Systems with KCU02 KSM02 KMS02 03 KMV03 KNK03 KLC03 ...
Страница 421: ...Notes IndraDrive Mi Drive Systems with KCU02 KSM02 KMS02 03 KMV03 KNK03 KLC03 407 407 ...