Mechanical Installation
ANCA Motion
DS619-0-00-0019 - Rev 0
25
4
4.
Mechanical Installation
4.1
What this Chapter Contains
This chapter contains information that is relevant to the mechanical installation of the drives in an electrical
cabinet such as
Pre installation checks
Installation site requirements
Tools required
Mounting and cooling
EMC armature cable shield termination
4.2
Pre installation checks
Prior to installing the drive into the electrical cabinet, check the information on the designation
label (located on the side of the drive). Please refer to section
3.4 AMD2000 Variant
Identification
.
Check that drive was not damaged during transport. If there are signs of damage the drive may
not be safe to use. Please notify shipper immediately of the damage and DO NOT install the
drive into the electrical cabinet.
4.3
Requirements
4.3.11
Installation Site
The AMD2000 Series Servo Drive must only be installed indoors, permanently fixed to the
electrical cabinet, and fitted by trained, qualified personnel.
Refer to the
4.3.13 Mounting and Cooling
for the correct installation process.
The safety precautions outlined in
1Safety
must be understood and adhered to.
The operating environment must not contain corrosive substances, metal particles, dust,
flammable substances or gases.
Ensure that there are no devices mounted adjacent to the drives that produce magnetic fields.
If you need to mount these devices next to the drives, ensure that there is a safe distance
between them or shield the magnetic fields.
The maximum recommended operating altitude is 1000m above sea level
The AMD20000 must not be installed in an environment in which the pollution degree
(according to IEC 61800) exceeds 2
Failure to follow these instructions may result in drive failure or degraded operation.
Refer to
12.6 Environmental Specifications
for further requirements