Power Wiring
ANCA Motion
DS619-0-00-0019 - Rev 0
35
6
6.
Power Wiring
6.1
What this Chapter Contains
This chapter contains information related to connecting the drive electrically to the incoming mains, motor and
brake as well as what to be mindful of such as:
Checking Assembly Insulation
Cable Connection and Earthing
Power Conditioning
Regenerative Brake Selection / Calculation
6.2
Checking the Insulation of the Assembly
Installed supply and motor cables must be tested for functioning insulation according to local regulations by using
an insulation resistance tester at 500V.
The AMD2000 drive has input supply voltage surge suppression components fitted to protect the drive from line
voltage transients typically originating from lightning strikes or switching of high power equipment on the same
supply. When carrying out a HiPot (Flash or megger) test on an installation in which the drive is built, the voltage
surge suppression components may cause the test to fail. To accommodate this type of system HiPot test, the
cables must be disconnected from the drive.
The cables to be disconnected and tested are: control voltage single phase supply (L1C/L2C), single-phase or
three-phase supply (L1/L2/L3), inductor connector (P1/P2), brake resistor connector (P/C/D) and motor connector
(U/V/W).
6.3
Mains Power Supply
The following components are required for connection to the mains supply:
Isolation switch to allow correct isolation of the system from the power supply
Fuse or circuit breakers to protect cables, filter and drive
Line filter (optional) to limit EMI on the mains supply
The mains control supply (LC1, LC2) for the drive requires a single phase supply which can be either two
phases from a 3 phase supply(120-220V line to line), or from a dedicated single phase supply (120-240V line to
neutral).
The mains power supply (L1, L2, L3) can be either from two or three phases of a three phase supply(120-220V
line to line), or a single phase supply (120-240V line to neutral)
The mains control supply can be linked the mains power supply allowing power to be applied at the same time.
External soft start circuitry is not required. The mains and control supply cables are terminated on the 6-way
connector as shown in
Figure 6-1
below.