426
Rockwell Automation Publication 2198-UM004A-EN-P - October 2019
Chapter 16
Troubleshoot the Kinetix 5100 Drive System
Table 130 - MOD LED Status Indicators
Operation Mode
LED Color
Status
Description
I/O
Steady off
No power
If no power is supplied to the device, the module status
indicator shall be steady off.
Steady green
Device operational
If the device is operating correctly (IO connection is established
successfully), the module status indicator shall be steady green.
Flashing green
Standby
If the device has not been configured, the module status
indicator shall be flashing green.
Flashing red
Major recoverable fault or
Minor recoverable fault
If the device has detected a major or minor recoverable fault,
the module status indicator shall be flashing red.
NOTE:
An incorrect or inconsistent configuration could be
considered a major recoverable fault.
Steady red
Major unrecoverable fault
If the device has detected a major unrecoverable fault, the
module status indicator shall be steady red.
Flashing green/red
Self-test
While the device is performing its power up testing, the module
status indicator shall be flashing green/red.
Standalone
Steady off
No power
If no power is supplied to the device, the module status
indicator shall be steady off.
Steady green
Device operational
If the device is operating correctly (after the drive boots
successfully), the module status indicator shall be steady green.
Flashing red
Major recoverable fault or
Minor recoverable fault
If the device has detected a major or minor recoverable fault,
the module status indicator shall be flashing red.
NOTE:
An incorrect or inconsistent configuration could be
considered a major recoverable fault.
Steady red
Major unrecoverable fault
If the device has detected a major unrecoverable fault, the
module status indicator shall be steady red.
Flashing green/red
Self-test
While the device is performing its power up testing, the module
status indicator shall be flashing green/red.
Table 131 - NET LED Status Indicators
LED Color
Status
Description
Steady off
No power or no IP address
The device is powered off, or is powered on but with no IP
address configured.
Steady green
Connected
An IP address is configured, at least one CIP™ connection (any
transport class) is established, and an Exclusive Owner
connection has not timed out.
Flashing green
Not connected
An IP address is configured but no CIP connections are
established, and an Exclusive Owner connection has not timed
out.
Flashing red
Connection timeout
An IP address is configured, and an Exclusive Owner connection
where this device is the target has timed out.
Steady red
A duplicate IP address has
been identified
The device has detected that (at least one of) its IP address is
already in use.
Flashing green/red
Self-test
While the device performs its power up testing.
Table 132 - CHARGE LED Status Indicators
LED Color
Status
Description
Steady off
No power
When no power is supplied to the device.
Steady orange
DC bus voltage operational
When the DC bus voltage is above 50V DC.
Содержание Kinetix 5100 2198-E1004-ERS
Страница 114: ...114 Rockwell Automation Publication 2198 UM004A EN P October 2019 Chapter 6 Set Up EtherNet IP Communication Notes ...
Страница 402: ...402 Rockwell Automation Publication 2198 UM004A EN P October 2019 Chapter 14 Absolute Position Recovery Notes ...
Страница 484: ...484 Rockwell Automation Publication 2198 UM004A EN P October 2019 Appendix C Use Add On Instructions Notes ...
Страница 488: ...488 Rockwell Automation Publication 2198 UM004A EN P October 2019 Appendix D Full Closed Loop Control Notes ...
Страница 499: ......