Rockwell Automation Publication 2198-UM004A-EN-P - October 2019
23
Plan and Install the Kinetix 5100 Drive System
Chapter 2
Circuit Breaker/Fuse Selection
The Kinetix 5100 drives use internal solid-state motor short-circuit protection
and, when connected to a suitable branch circuit protection, are rated for use on a
circuit that can deliver up to 5000 A (fuses or circuit breakers).
Make sure the selected components are properly coordinated and meet
acceptable codes including any requirements for branch circuit protection.
Evaluation of the short-circuit available current is critical and must be kept below
the short-circuit current rating of the circuit breaker.
See the Kinetix Servo Drives Specifications Technical Data, publication
, for input current and inrush current specifications for your
Kinetix 5100 drive.
Circuit Breaker/Fuse Specifications
Kinetix 5100 servo drives use internal solid-state motor short-circuit protection
and, when protected by suitable branch circuit protection, are rated for use on a
circuit capable of delivering up to 5000 A when protected by fuses or circuit
breakers. These fuses and Allen-Bradley circuit breakers are recommended for use
with 2198-E
xxxx
-ERS drives.
Table 5 - Control Power Circuit-protection Specifications
IMPORTANT
Do not use circuit protection devices on the output of an AC drive as an
isolating disconnect switch or motor overload device. These devices are
designed to operate on sine-wave voltage and the drive's PWM waveform does
not allow it to operate properly. As a result, damage to the device occurs.
Cat. No.
Fuse (Bussman)
Cat. No
Circuit breaker
Cat. No.
2198-E1004-ERS
KTK-R-2 (2 A)
1489-M2D010
2198-E1007-ERS
2198-E1015-ERS
2198-E1020-ERS
1489-M2D020
2198-E2030-ERS
1489-M2D010
2198-E2055-ERS
KTK-R-3 (3 A)
1489-M2D016
2198-E2075-ERS
2198-E2150-ERS
KTK-R-5 (5 A)
1489-M2D030
Содержание Kinetix 5100 2198-E1004-ERS
Страница 114: ...114 Rockwell Automation Publication 2198 UM004A EN P October 2019 Chapter 6 Set Up EtherNet IP Communication Notes ...
Страница 402: ...402 Rockwell Automation Publication 2198 UM004A EN P October 2019 Chapter 14 Absolute Position Recovery Notes ...
Страница 484: ...484 Rockwell Automation Publication 2198 UM004A EN P October 2019 Appendix C Use Add On Instructions Notes ...
Страница 488: ...488 Rockwell Automation Publication 2198 UM004A EN P October 2019 Appendix D Full Closed Loop Control Notes ...
Страница 499: ......