220
Rockwell Automation Publication 2198-UM004A-EN-P - October 2019
Chapter 10
Modes of Operation
If the resonance frequency is given, the notch filter can mitigate the resonance
directly. Frequency of notch filter is 50…5000 Hz and the suppression strength is
0…40 dB. If the frequency meets this condition, using low pass filter to reduce the
resonance is suggested.
Auto-resonance Suppression Mode
Settings:
X: Auto-resonance Suppression Function
0 = Disable auto resonance suppression. After the function is disabled, the
existing resonance suppression parameter values are fixed.
1 = Auto resonance suppression. The servo must determine the following:
Y: Fixed Resonance Suppression Parameter
In auto resonance suppression, you can set the notch filters that require manual
resonance suppression.
Table 81 - Relevant Parameter
Parameter
Name
ID230 (P2.047)
ResonanceSuppressionConfig
X = Auto-resonance
Suppression
Function
Y = Fixed Resonance
Suppression
Parameter
Z = Fixed Resonance
Suppression
Parameter
U = Reserved
Where:
See below
See below
See below
If
Then
• The servo is stable and resonance is suppressed
• No other resonance is present
• No other interference source is present
The servo automatically saves the data of resonance
suppression, and the value returns to 0.
If the servo is unstable, re-power on or set to 1 again
for the servo to re-estimate.
Bit
Function
Description
0
Notch 1 auto/manual setting
• 0: Auto resonance suppression
• 1: Manually set the first set of resonance suppression
1
Notch 2 auto/manual setting
• 0: Auto resonance suppression
• 1: Manually set the second set of resonance suppression
2
Notch 3 auto/manual setting
• 0: Auto resonance suppression
• 1: Manually set the third set of resonance suppression
3
Notch 4 auto/manual setting
• 0: Auto resonance suppression
• 1: Manually set the fourth set of resonance suppression
Содержание Kinetix 5100 2198-E1004-ERS
Страница 114: ...114 Rockwell Automation Publication 2198 UM004A EN P October 2019 Chapter 6 Set Up EtherNet IP Communication Notes ...
Страница 402: ...402 Rockwell Automation Publication 2198 UM004A EN P October 2019 Chapter 14 Absolute Position Recovery Notes ...
Страница 484: ...484 Rockwell Automation Publication 2198 UM004A EN P October 2019 Appendix C Use Add On Instructions Notes ...
Страница 488: ...488 Rockwell Automation Publication 2198 UM004A EN P October 2019 Appendix D Full Closed Loop Control Notes ...
Страница 499: ......