Enclosure Selection
This example is provided to assist you in size selection for an enclosure for your
Kinetix 5100 drive system. You need heat dissipation data from all components
that are planned for your enclosure to calculate the enclosure size. See
for the Kinetix 5100 drive heat dissipation specifications.
With no active method of heat dissipation (such as fans or air conditioning),
either of the following approximate equations can be used.
If the maximum ambient rating of the Kinetix 5100 drive system is 50 °C
(122 °F) and if the maximum environmental temperature is 20 °C (68 °F), then
T=30. In this example, the total heat dissipation is 416 W (sum of all
components in enclosure). So, in the equation below, T=30 and Q=416.
In this example, the enclosure must have an exterior surface of at least 2.99 m
2
. If
any portion of the enclosure is not able to transfer heat, do not include that value
in the calculation.
Because the minimum cabinet depth to house the Kinetix 5100 system (selected
for this example) is 300 mm (11.8 in.), the cabinet needs to be approximately
1500 x 700 x 300 mm (59.0 x 27.6 x 11.8 in.) HxWxD.
1.5 x (0.300 x 0.70) + 1.5 x (0.300 x 2.0) + 1.5 x (0.70 x 2.0) = 3.31 m
2
Because this cabinet size is considerably larger than what is necessary to house the
system components, it can be more efficient to provide a means of cooling in a
smaller cabinet. Contact your cabinet manufacturer for options available to cool
your cabinet.
Metric
Standard English
Where T is temperature difference between inside air
and outside ambient (°C), Q is heat that is generated in
enclosure (Watts), and A is enclosure surface area (m
2
).
The exterior surface of all six sides of an enclosure is
calculated as
Where T is temperature difference between inside air
and outside ambient (°F), Q is heat that is generated in
enclosure (Watts), and A is enclosure surface area (ft
2)
.
The exterior surface of all six sides of an enclosure is
calculated as
A = 2dw + 2dh + 2wh
A = (2dw + 2dh + 2wh) /144
Where d (depth), w (width), and h (height) are in
meters.
Where d (depth), w (width), and h (height) are in inches.
A
= 0.38
Q
1.8
T
- 1.1
A
= 4.08
Q
T
- 1.1
A = 0.38 (416)
1.8 (30) - 1.1
= 2.99 m
2
Содержание Kinetix 5100 2198-E1004-ERS
Страница 114: ...114 Rockwell Automation Publication 2198 UM004A EN P October 2019 Chapter 6 Set Up EtherNet IP Communication Notes ...
Страница 402: ...402 Rockwell Automation Publication 2198 UM004A EN P October 2019 Chapter 14 Absolute Position Recovery Notes ...
Страница 484: ...484 Rockwell Automation Publication 2198 UM004A EN P October 2019 Appendix C Use Add On Instructions Notes ...
Страница 488: ...488 Rockwell Automation Publication 2198 UM004A EN P October 2019 Appendix D Full Closed Loop Control Notes ...
Страница 499: ......