In order to adapt to the previous relay characteristic the above equation can be re-
written in the following way:
[ ]
01
1
1
0
so
s
so
t
K
I
s
T
I
I
æ
ö
ç
÷
ç
÷
=
+
×
ç
÷
æ
ö
ç
÷
-
ç
÷
ç
÷
è
ø
è
ø
EQUATION13000032 V1 EN
(Equation 260)
Thus if the following rules are followed when multi-purpose overcurrent stage one is
set:
•
in
>
= I
S0
= 300A
•
35566
118.55
300
so
A
K
I
=
=
=
•
01
0.64
B
T
=
=
•
0.0
C
=
•
1.0
p
=
•
1.0
k
=
then exact replica of the existing relay will be achieved. The following table
summarizes all required settings for the multi-purpose function:
Setting Group1
Operation
On
CurrentInput
MaxPh
IBase
1000
VoltageInput
MaxPh
UBase
20.50
OPerHarmRestr
Off
I_2ndI_fund
20.0
BlkLevel2nd
5000
EnRestrainCurr
Off
RestrCurrInput
PosSeq
RestrCurrCoeff
0.00
RCADir
-75
ROADir
75
LowVolt_VM
0.5
Section 13
1MRK 502 071-UEN -
System protection and control
468
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual